Skip to main content

What is Arc Flash Studies?How it is carried out?




In order to identify the specific arc flash hazard at a given piece of equipment within a  given facility, an arc flash study must be performed.

Outcome of Arc flash Study?

  • Identify the Arc Flash Protection Boundary (this is the closest approach allowed before PPE must be worn). 
  • arc flash equipment labeling
  • Fault current and coordination analysis
  •  recommendations for PPEs
  • Arc Flash Incident Energy Mitigation Strategies

How Arc flash Study carried out?

There are several software packages available, similarly to short circuit study and coordination study software packages, to facilitate this analysis by a qualified professional electrical engineer. 

Following seven steps to be carried out to done complete Arc flash study of the facility.

     1.Gathering all as built documentation of the facility


The starting point of study is to accumulate all documentation like Electrical and earthing drawing etc.
If the old drawing not found than sinle-line diagram to be made of the system.

     2.Field verification as per documentation
Before loading the data from the electrical drawings into the Arc Flash Analysis software, the drawings must be field verified. This requires a survey of each site to verify one-line documentation and document any missing information in order to generate an encompassing and accurate one-line.
Equipment covers need to come off so we can visually inspect and acquire PD (protective device) manufacturer/types/sizes/settings, cable type/lengths, transformer impedance values, and KVA sizes. Look below for types of equipment surveyed.

    3.Acquire load information

After the field survey is complete and the information on the drawings has been verified, this information is then loaded into our software package (Example:SKM Power Tools) to run the Short Circuit, Coordination, and Arc Flash analysis 


    4.Run a short-circuit study

Once the data has been loaded into software, we review the L-L-L-E and L-E line to ground fault currents against the protective device “duty rating” to ensure the device can clear the fault. 
If a fault occurs at any given protective device, the value of the duty rating is the amount of fault current the device can handle and clear the fault in what we call a “bolted fault”.  
In other words, if the available fault current is less than the duty rating of the device, the device will do what it is intended and manufactured to do (clear it). 
If the fault currents are more than the duty rating, the device will likely fail and cause an arc flash incident.
    5.Perform a coordination study.

In a properly coordinated system, the nearest protective device upstream of the fault will clear the fault without affecting protective devices further upstream.  This will limit the impact of a fault on the overall electrical distribution only to where the fault is located.

In order to be assured that all over current protection devices are coordinated, it is necessary to look at the time vs. current characteristics of each device and compare it to the characteristics of any upstream devices.


    6.Evaluate Equipment

When applicable, we provide recommendations to lower the incident energy levels including maximizing coordination.  

How we do this and as mentioned in section 5 above, for those protective devices that have the option of making setting adjustments, we can adjust for both; good coordination and lowering of “incident energy levels”.  


    7.Arc flash study conclusion

Completing the Arc Flash study includes:
  • Generating and applying the Arc Flash labels
  • Training of the electrical staff
  • PPEs rating and usage
  • Arc flash labeling
  • Training to the asset facing people

Comments

Popular posts from this blog

Dielectric frequency response (DFR) analysis for moisture measurement in transformer

The dielectric response is a unique characteristic of the particular insulation system. The increased moisture content of the insulation results in a changed dielectric model and, consequently, a changed dielectric response. By measuring the dielectric response of the equipment in a wide frequency range, the moisture content can be assessed and the insulation condition diagnosed. The test connections and modes are the same as used in a traditional transformer insulation power-factor test with the difference being the test is performed at a low voltage, up to 200 Vp-p, and the test is performed at frequencies from 1 kHz to 1μHz .  In this Figure the response curve for oil-impregnated paper. This curve shows a frequency vs. dissipation factor relationship. The higher frequencies display the moisture and aging of the cellulose. Moving from left to right the frequency is reduced and the oil conductivity properties are displayed. In the millihertz range, the ...

RCM(Reliability Centered Maintenance):Basic Seven Questions to be asked

To evaluate any asset or system with the RCM(Reliability Centered Maintenance) process Following seven questions are to be asked, What are the functions and associate performance standards of the system in present operating condition? How the system is failed to fulfill its functions? What are the causes for the failure of its functions.? What happen when its function failure occurred? In what way each failure matter or failure significance or consequences? What can be done to prevent or predict the failure? What happen if any proper proactive task cannot be found to prevent or predict the failure? Any team ask this basic Seven question to the system or the asset to be evaluated via RCM process for determination the maintenance requirement to be done easily. #RCM #realibility