Skip to main content

What is Arc Flash Studies?How it is carried out?




In order to identify the specific arc flash hazard at a given piece of equipment within a  given facility, an arc flash study must be performed.

Outcome of Arc flash Study?

  • Identify the Arc Flash Protection Boundary (this is the closest approach allowed before PPE must be worn). 
  • arc flash equipment labeling
  • Fault current and coordination analysis
  •  recommendations for PPEs
  • Arc Flash Incident Energy Mitigation Strategies

How Arc flash Study carried out?

There are several software packages available, similarly to short circuit study and coordination study software packages, to facilitate this analysis by a qualified professional electrical engineer. 

Following seven steps to be carried out to done complete Arc flash study of the facility.

     1.Gathering all as built documentation of the facility


The starting point of study is to accumulate all documentation like Electrical and earthing drawing etc.
If the old drawing not found than sinle-line diagram to be made of the system.

     2.Field verification as per documentation
Before loading the data from the electrical drawings into the Arc Flash Analysis software, the drawings must be field verified. This requires a survey of each site to verify one-line documentation and document any missing information in order to generate an encompassing and accurate one-line.
Equipment covers need to come off so we can visually inspect and acquire PD (protective device) manufacturer/types/sizes/settings, cable type/lengths, transformer impedance values, and KVA sizes. Look below for types of equipment surveyed.

    3.Acquire load information

After the field survey is complete and the information on the drawings has been verified, this information is then loaded into our software package (Example:SKM Power Tools) to run the Short Circuit, Coordination, and Arc Flash analysis 


    4.Run a short-circuit study

Once the data has been loaded into software, we review the L-L-L-E and L-E line to ground fault currents against the protective device “duty rating” to ensure the device can clear the fault. 
If a fault occurs at any given protective device, the value of the duty rating is the amount of fault current the device can handle and clear the fault in what we call a “bolted fault”.  
In other words, if the available fault current is less than the duty rating of the device, the device will do what it is intended and manufactured to do (clear it). 
If the fault currents are more than the duty rating, the device will likely fail and cause an arc flash incident.
    5.Perform a coordination study.

In a properly coordinated system, the nearest protective device upstream of the fault will clear the fault without affecting protective devices further upstream.  This will limit the impact of a fault on the overall electrical distribution only to where the fault is located.

In order to be assured that all over current protection devices are coordinated, it is necessary to look at the time vs. current characteristics of each device and compare it to the characteristics of any upstream devices.


    6.Evaluate Equipment

When applicable, we provide recommendations to lower the incident energy levels including maximizing coordination.  

How we do this and as mentioned in section 5 above, for those protective devices that have the option of making setting adjustments, we can adjust for both; good coordination and lowering of “incident energy levels”.  


    7.Arc flash study conclusion

Completing the Arc Flash study includes:
  • Generating and applying the Arc Flash labels
  • Training of the electrical staff
  • PPEs rating and usage
  • Arc flash labeling
  • Training to the asset facing people

Comments

Popular posts from this blog

Sweep Frequency Response Analysis Test | SFRA Test of Transformer

What is SFRA Test? Frequency response analysis (often referred to as FRA or SFRA ) is a powerful and sensitive method for testing the mechanical integrity of transformer cores, windings, and press frames, in power transformers. The winding of transformer may be subjected to mechanical stresses during transportation, heavy short circuit faults, transient switching impulses and lightening impulses etc. These mechanical stresses may cause displacement of transformer windings from their position and may also cause deformation of these windings. SFRA Test can detect, winding deformation – axial & radial, like hoop buckling, tilting, spiraling displacements between high and low voltage windings partial winding collapse shorted or open turns faulty grounding of core or screens core movement broken clamping structures problematic internal connections How SFRA works? Transformers consist of multiple complex networks of capacitances and resistors that can generate a unique ...

Why VLF testing is preferred than conventional DC testing in Diagnostic field?

Testing of cable with conventional method is "DC hipod" testing.A considerable rise in premature failures was observed when polymeric cables (XLPE, EPR, etc.) were introduced into the electric grid and readily being tested with DC. This failure with DC hi-Pot testing is cause of trapped charge within the defects of Insulation due to intense charge migration via Unidirectional DC field When DC test completed and AC supply applied to the cable this charge lead to rapid generation of electrical tree and subsequent failure. VLF testing benefits Potential failures should happen during the actual test so that repairs can be made immediately because test time of VLF testing is more about 15 min to 60 min. Lower power and current requirement for testing which significantly reduced size/weight to allow for a very portable high voltage tester. Both benefits describes briefly as below, Under DC test, test object remain less time under voltage stress than VLF test...

How to calculate restraining quantity in Differential relay during testing

Here I'm providing the equation for calculate restraining quantity in differential relay. %restrain= I diff setting + (I1 * CT1 error) + (I2 * CT2 error) I diff setting =Differential setting in relay(ex. 0.2Amp) I1 =Current injected in CT for 1 end relay for testing I2 =Current injected in CT for 2 end relay for testing Ct erro r=5%(if injected current <1) OR 15%(if Injected current >=1) During testing we found Ij1=Ij2, because generally same current is seen during fault bay both end relay Case-1 Injected current=1Amp,I differ setting=0.2( Assume CT error 15% when Injected current >=1) %restrain= I diff setting + (I1 * CT1 error) + (I2 * CT2 error)                    =0.2 +(1 * 0.15) + (1 * 0.15)                    =0.50   %restrain =50%(around) Cas...