Skip to main content

Dielectric frequency response (DFR) analysis for moisture measurement in transformer


The dielectric response is a unique characteristic of the particular insulation system. The increased moisture content of the insulation results in a changed dielectric model and, consequently, a changed dielectric response. By measuring the dielectric response of the equipment in a wide frequency range, the moisture content can be assessed and the insulation condition diagnosed.

The test connections and modes are the same as used in a traditional transformer insulation power-factor test with the difference being the test is performed at a low voltage, up to 200 Vp-p, and the test is performed at frequencies from 1 kHz to 1μHz. 

In this Figure the response curve for oil-impregnated paper. This curve shows a frequency vs. dissipation factor relationship.
  • The higher frequencies display the moisture and aging of the cellulose.
  • Moving from left to right the frequency is reduced and the oil conductivity properties are displayed. In the millihertz range, the insulation geometry comes into play.
  • As the moisture properties of the cellulose change so does the shape of the curve.
The most common techniques used to measure this response are frequency domain spectroscopy (FDS) and polarization and depolarization current (PDC) methods. Using the frequency domain spectroscopy, the dissipation factor of the insulation system under test is measured by frequency sweep. The FDS allows fast measurements at high frequencies but requires long measurement times at frequencies down to 0.1 millihertz.
After the test is completed the results must be compared to a standard to determine the actual moisture content. IEC 60422 and IEEE 62-1995 have defined moisture classifications.

Comments

Popular posts from this blog

How to calculate restraining quantity in Differential relay during testing

Here I'm providing the equation for calculate restraining quantity in differential relay. %restrain= I diff setting + (I1 * CT1 error) + (I2 * CT2 error) I diff setting =Differential setting in relay(ex. 0.2Amp) I1 =Current injected in CT for 1 end relay for testing I2 =Current injected in CT for 2 end relay for testing Ct erro r=5%(if injected current <1) OR 15%(if Injected current >=1) During testing we found Ij1=Ij2, because generally same current is seen during fault bay both end relay Case-1 Injected current=1Amp,I differ setting=0.2( Assume CT error 15% when Injected current >=1) %restrain= I diff setting + (I1 * CT1 error) + (I2 * CT2 error)                    =0.2 +(1 * 0.15) + (1 * 0.15)                    =0.50   %restrain =50%(around) Cas...

What is Arc Flash Studies?How it is carried out?

In order to identify the specific arc flash hazard at a given piece of equipment within a  given facility, an arc flash study must be performed. Outcome of Arc flash Study? Identify the Arc Flash Protection Boundary (this is the closest approach allowed before PPE must be worn).  arc flash equipment labeling Fault current and coordination analysis  recommendations for PPEs Arc Flash Incident Energy Mitigation Strategies How Arc flash Study carried out? There are several software packages available, similarly to short circuit study and coordination study software packages, to facilitate this analysis by a qualified professional electrical engineer.  Following seven steps to be carried out to done complete Arc flash study of the facility.      1.Gathering all as built documentation of the facility The starting point of study is to accumulate  all documentation like Electrical and earthing drawing etc. If...