Skip to main content

Sweep Frequency Response Analysis Test | SFRA Test of Transformer




What is SFRA Test?

Frequency response analysis (often referred to as FRA or SFRA) is a powerful and sensitive method for testing the mechanical integrity of transformer cores, windings, and press frames, in power transformers.

The winding of transformer may be subjected to mechanical stresses during transportation, heavy short circuit faults, transient switching impulses and lightening impulses etc. These mechanical stresses may cause displacement of transformer windings from their position and may also cause deformation of these windings.

SFRA Test can detect,
  • winding deformation – axial & radial, like hoop buckling, tilting, spiraling
  • displacements between high and low voltage windings
  • partial winding collapse
  • shorted or open turns
  • faulty grounding of core or screens
  • core movement
  • broken clamping structures
  • problematic internal connections

How SFRA works?

Transformers consist of multiple complex networks of capacitances and resistors that can generate a unique signature when tested at discreet frequencies and plotted as a curve.

The term 'theoretically' means in most cases the resistance, inductance and capacitance of an equipment have non zero values. Hence most of the electrical equipment can be considered as RLC circuit hence they response to the sweep frequencies and produce an unique signature.

As in a transformer each winding turn is insulated from other by paper insulation which acts as dielectric and winding themselves have inductance and resistance, hence a transformer became as a complicated distributed network of R,L and C or in other words a transformer is a complicated RLC circuit.


Now in SFRA sinusoidal voltage Vi is applied to one end of a winding and output voltage Vo is measured at the other end of the winding. Remaining windings are kept open. As the winding is itself an distributed RLC circuit it will behave like RLC filter and gives different output voltages at different frequencies.

Here if we make constant input voltage Vi and change different frequency than according to the complexity of each winding we can find different output voltage Vo with different frequency.Each winding have unique signature of frequency Vs Output voltage graph.


But after transportation, heavy short circuit faults, transient switching impulses and lightening impulses etc, if we do same Sweep Frequency Response Analysis test and superimpose the present signature with the earlier patterns and observe some deviation between these tow graphs, we can asses that there is mechanical displacement and deformation occurred in the winding.

#ElectricalReliability #tranformerTesting #SFRA

Comments

Popular posts from this blog

Why VLF testing is preferred than conventional DC testing in Diagnostic field?

Testing of cable with conventional method is "DC hipod" testing.A considerable rise in premature failures was observed when polymeric cables (XLPE, EPR, etc.) were introduced into the electric grid and readily being tested with DC. This failure with DC hi-Pot testing is cause of trapped charge within the defects of Insulation due to intense charge migration via Unidirectional DC field When DC test completed and AC supply applied to the cable this charge lead to rapid generation of electrical tree and subsequent failure. VLF testing benefits Potential failures should happen during the actual test so that repairs can be made immediately because test time of VLF testing is more about 15 min to 60 min. Lower power and current requirement for testing which significantly reduced size/weight to allow for a very portable high voltage tester. Both benefits describes briefly as below, Under DC test, test object remain less time under voltage stress than VLF test

How to calculate restraining quantity in Differential relay during testing

Here I'm providing the equation for calculate restraining quantity in differential relay. %restrain= I diff setting + (I1 * CT1 error) + (I2 * CT2 error) I diff setting =Differential setting in relay(ex. 0.2Amp) I1 =Current injected in CT for 1 end relay for testing I2 =Current injected in CT for 2 end relay for testing Ct erro r=5%(if injected current <1) OR 15%(if Injected current >=1) During testing we found Ij1=Ij2, because generally same current is seen during fault bay both end relay Case-1 Injected current=1Amp,I differ setting=0.2( Assume CT error 15% when Injected current >=1) %restrain= I diff setting + (I1 * CT1 error) + (I2 * CT2 error)                    =0.2 +(1 * 0.15) + (1 * 0.15)                    =0.50   %restrain =50%(around) Case-2 Injected current=0.5Amp,I differ setting=0.2 ( Assume CT error 5% when Injected current <1) %restrain= I diff setting + (I1 * CT1 error) + (j2 * CT2 error)